19 AWG 2P Stranded BC Shield Al Tape PE Armour PVC RE-2Y(St)YRY 300V Instrumentation Cable
Original price was: $10.00.$8.00Current price is: $8.00.
(In Stock)
[pdf] [/pdf]
19 AWG 2P Stranded BC Shield Al Tape PE Armour PVC RE-2Y(St)YRY 300V Instrumentation Cable
Allowable Ampacityfor 19 AWG 2P Stranded BC Shield Al Tape PE Armour PVC RE-2Y(St)YRY 300V Instrumentation Cable:100 Amps
About:
This cable features a 19 American Wire Gauge (AWG) single pair (2P) configuration, which is ideal for transmitting signals with minimal loss or interference. Its design is tailored for environments where reliability and durability are crucial, particularly in industrial and process control applications.
Also Known As:
This type of cable might be known under different names based on regional or manufacturer-specific nomenclature but is generally recognized by its specific construction details and application purpose, often simply referred to by its construction and electrical characteristics.
Application:
These cables are used for transmission of analoge and digital signals in instrument and control systems at chemistry and petrochemistry industry plants, natural gas and petroleum plants. With blue sheath it is suitable for intrinsically safe systems. these cables are for indoor/outdoor installation, in dry and wet locations, on rack trays, in conduits.
Standards:
Likely conforms to certain IEC, EN, or VDE standards, which govern its construction, performance, and testing criteria.
Designed to meet 300V specification, suitable for various instrumentation and control applications.
Construction:
Conductor:Stranded red copper conductor Cl. 2, acc. to IEC 60228, DIN VDE 0295
Insulation: PE compound
Colour cores:white-black, with black progressively numbered
Stranding:Conductors twisted in pairs
Wrapping:Polyester tape
Screen:Electrostatic screen of plastic and aluminium tape + tinned drain-wire
Inner Sheath:PVC compound
Armour:Galvanized steel wires
Outer Sheath:black (RAL 9005), or blue (RAL 5015), special PVC compound
Features:
fl:On Request
Standard TS/DIN EN 50288-7
Insulation thickness:mm 0,50 0,75 1 1,3 1,5
mm 0,40 0,40 0,40 0,45 0,45
Conductor Resistance:mm 0,50 0,75 1 1,3 1,5
Ohm/km 36,7 25 18,5 14,2 12,3
Insulation Resistance:min. 5 GOhm x km
Mutual Capacitance: 4 pairs all other pairs
0,50 mm2: max. 115 pF/m max. 90 pF/m
0,75 mm2: max. 115 pF/m max. 90 pF/m
1,0 mm2: max. 115 pF/m max. 90 pF/m
1,3 mm2: max. 120 pF/m max. 105 pF/m
1,5 mm2: max. 120 pF/m max. 105 pF/m
Capacitance Unbalance:(1 kHz): max. 500 pF/500 m
L/R (oran-ratio) (max.):mm 0,50 0,75 1.0 1,3 1,5
mm 25 25 25 40 40
Specifications:
No. of pairs x cross section n x mm: 2x2x0,75
AWG no.: 19
Outer- ca.mm 10%: 13,4
Copper Weight kg/km: 34
Nominal Voltage:300 V
Test Voltage:2 kV
Temperature Range:– 30 C up to + 70 C
Min. bending radius:10 x d
Cable Weight approx. kg/km: 295
Part Number: 47140C.X022M07