4/0 AWG 1C Stranded Bare Copper Tape Shield Armour Al PVC RE4H1RFR 3.6/6KV Medium Voltage Cable
Original price was: $10.00.$8.00Current price is: $8.00.
(In Stock)
[pdf] [/pdf]
4/0 AWG 1C Stranded Bare Copper Tape Shield Armour Al PVC RE4H1RFR 3.6/6KV Medium Voltage Cable
Allowable Ampacityfor 4/0 AWG 1C Stranded Bare Copper Tape Shield Armour Al PVC RE4H1RFR 3.6/6KV Medium Voltage Cable:100 Amps
About:
This type of cable is designed to transmit electricity at medium voltages, typically between 3.6 and 6 kilovolts. It is made with a single conductor (1C) of 4/0 American Wire Gauge (AWG) size, using stranded bare copper for flexibility and effective conductivity.
Also Known As:
It might be known by various names depending on the manufacturer or the region, focusing on its key components like 4/0 AWG, stranded copper, tape shield, aluminum armor, and PVC jacket, among others.
Application:
Power distribution in industrial settings
Infrastructure such as substations and power plants
Connection of electrical equipment and transformers
Indoor and outdoor applications, given its protective armor and insulation
Standards:
IEC (International Electrotechnical Commission) standards for medium voltage cables
ASTM (American Society for Testing and Materials) standards for the quality of the copper and aluminum used
Local or regional standards regarding electrical installations and safety
Construction:
Conductor:Stranded Red Copper Conductor Cl.2, acc.to IEC 60228
Inner Semi-Conductive Layer:Extruded Semi-Conducting Compound
Insulation: XLPE compound
Outer Semi-Conductive Layer:Extruded Semi-Conducting Compound
Screen:Red Copper Tape
Inner Sheath:PVC Compound
Armour:Aluminium wires
Outer Sheath:Red (RAL 3000), PVC type ST2
Features:
According to IEC 60502-2
Specifications:
No. of cores x cross section n x mm: 1×120
AWG no.: 4/0
Outer- ca.mm 10%: 30,5
Nominal Voltage:Uo/U 3,6/6 kV, Uo/U 6/10 kV, Uo/U 8,7/15 kV, Uo/U 12/20 kV, Uo/U 18/30 kV
Test Voltage:Uo/U 3,6/6 kV = 11 kV, Uo/U 6/10 kV = 17 kV, Uo/U 8,7/15 kV = 24 kV, Uo/U 12/20 kV= 29 kV, Uo/U 18/30 kV = 45 kV
Temperature range:– 0 C up to + 90 C
Max short circuit temperature:+ 250 C
Min. Bending Radius:14 x d
Cable Weight approx. kg/km: 1970
Part Number: 48110MRL010M68
Reviews